GE FVP110 Maintenance Manual page 224

Table of Contents

Advertisement

GE Energy
Relative
Index
Parameter
Index
41
8041
FF_SCALE
42
8042
FF_GAIN
43
8043
UPDATE_EV
T
44
8044
BLOCK_ALM
45
8045
ALARM_SUM Enable
46
8046
ACK_OPTIO
N
47
8047
ALARM_HYS
48
8048
HI_HI_PRI
49
8049
HI_HI_LIM
50
8050
HI_PRI
51
8051
HI_LIM
52
8052
LO_LO_PRI
53
8053
LO_LO_LIM
54
8054
LO_PRI
55
8055
LO_LIM
56
8056
DV_HI_PRI
57
8057
DV_HI_LIM
58
8058
DV_LO_PRI
59
8059
DV_LO_LIM
Table 65 PID Block Parameters (Continued)
Default
Name
(factory
setting)
0-100%
0
0XFFFF
0.5%
0
+INF
0
+INF
0
+INF
0
+INF
0
+INF
0
+INF
FVP 110 Fieldbus Valve Positioner Manual
Write
Man
Scale limits used for converting the FF_VAL
value to a non-dimensional value.
Man
Gain for FF_VAL.
Shows the contents of an update event upon
occurrence.
Shows the contents of a block alarm upon
occurrence.
Shows the alarm summary (current alarm
statuses, acknowledged/unacknowledged
states, masking states)
Selects whether or not the alarms related to the
DI block are automatically self-acknowledged.
Hysteresis for alarm detection and resetting to
prevent each alarm from occurring and
recovering repeatedly within a short time.
Priority order of HI_HI_ALM alarm.
Setting for HI_HI_ALM alarm.
Priority order of HI_ALM alarm.
Setting for HI_ALM alarm.
Priority order of LO_ALM alarm.
Setting for LO_ALM alarm.
Priority order of LO_LO_ALM alarm.
Setting for LO_LO_ALM alarm
Priority order of DV_HI_ALM alarm.
Setting for DV_HI_ALM alarm.
Priority order of DV_LO_ALM alarm.
Setting for DV_LO_ALM alarm.
208
Description

Hide quick links:

Advertisement

Table of Contents
loading