Parameters of Transducer Block
Relative
Index
Parameter
Index
6
2006
BLOCK_ERR
7
2007
UPDATE_
EVT
8
2008
BLOCK_ALM
9
2009
TRANSDUCE
R
_DIRECTOR
Y
10
2010
TRANSDUCE
R_TYPE
11
2011

XD_ERROR

12
2012
CORRECTIO
N
_DIRCTORY
13
2013
FINAL_
VALUE
14
2014
FINAL_
VALUE
_RANGE
15
2015
FINAL_
VALUE
_CUTOFF_HI
16
2016
FINAL_
VALUE
_CUTOFF_
LO
17
2017
FINAL_
POSITION
_VALUE
Table 61 Transducer Block Parameters (Continued)
Default
Name
(factory
setting)
1, 10
106
0
1, 13
-10%, 110%
110%
-10%
Write
Indicates the error statuses related to the block
itself.
Shows the contents of an update event upon
occurrence.
Universal parameter indicating the hardware
and software error statuses related to the block
itself.
Index to the text describing the transducer
contained in the FVP110 positioner.
Transducer type.
Stores the error prioritized at the highest level
from among the errors that are currently
occurring in the transducer block.
Stores the number of data collection and the
index number to be started with.
O/S
Stores the valve control level and status written
by the AO block.
O/S
Defines the upper and lower range limits of
FINAL_VALUE, and the unit code and decimal
point position for value indication of
INAL_VALUE.
O/S
If the value of FINAL_VALUE is greater than
the value set in this parameter, the FVP110
moves the valve to the full-open position.
O/S
If the value of FINAL_VALUE is less than the
value set in this parameter, the FVP110 moves
the valve to the shut-off position.
Stores the position data read by the valve
position sensor.
189
Function Block Parameters
Description