Monitoring System - Huawei FusionModule 1000B Maintenance Manual

Air-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
Item
Thermal
insulation
foam for
the
humidifier/
condensate
drainpipe

4.3.3 Monitoring System

When you check the hydrogen sensor in the container, only a small amount of hydrogen needs
to be released onto the sensor. During the entire process, flames and sparks are prohibited in
or around the power supply and battery compartments.
Issue 02 (2017-01-10)
Method
Expected
Result
misshapen.
Check electric
The electric
heaters.
heaters and
switches are
secure.
The electric
heater surface
is not
corroded.
Check the
Check that T/H
temperature-humid
sensors in the
ity sensor.
air conditioner
and aisles are
securely
installed.
Check the water
The water
sensor.
sensor is
secure, and the
two downward
metal
conductive
plates do not
touch with
each other and
are free from
corrosion.
Check whether the
The thermal
thermal insulation
insulation
layers are in good
layers are in
condition without
good condition
condensation.
and free from
condensation.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Routine Maintenance
Troubleshooting
Secure the electric heaters and
switches.
Replace the faulty electric heater by
following instructions in the air
conditioner user manual.
Secure the T/H sensor.
Replace the faulty water sensor by
following instructions in the air
conditioner user manual.
If there is condensate water under
the pipe, replace by following
instructions in
6.2.6 Replacing a
Thermal Insulation
Layer.
27