FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
Table 4-5 Monthly maintenance checklist for the monitoring system
Item
Event and
operation
logs in the
RH2288
server
ECC500
collector
VCN500
Access
control
system
Hydrogen
detection
system
Issue 02 (2017-01-10)
Method
Expected
Result
Choose System
Normal system
Event Log in the
events are
navigation tree.
displayed.
Check the
The running
indicators of the
indicator is
ECC500 main
steady on.
control module.
Check the
The VCN500
VCN500 indicator.
indicator is
steady green.
Swipe a card to
When an
open the door.
access card is
swiped, the
card reader
indicator
blinks green
once and then
returns to
steady red.
You will hear
a beep.
Press the exit
The door can
button and open
be opened.
the door.
Check the
The normal
hydrogen density
value is 0% or
that is displayed.
1%.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Routine Maintenance
Troubleshooting
See the documents delivered with
the RH2288 server.
If the running indicator is
blinking quickly, check the
power supply or the
communications cable between
the ECC500 and the host.
If the alarm indicator is on, view
and handle the alarms.
See the documents delivered with
the VCN500.
Swipe another access card and
observe the door status:
If the door can be opened by
another access card, the original
access card is damaged. Prepare
a new access card and assign
permission to the card.
If the door cannot be opened,
replace by following instructions
in
6.3.13.1 Replacing a Card
Reader.
1. Check whether the cable to the
exit button is properly
connected.
2. If the fault persists, replace by
following instructions in
Replacing an Exit
Button.
1. If the density is abnormal, open
the door to ventilate the
container for 4 hours.
2. If the fault persists, contact
Huawei technical support.
6.3.13.2