Huawei FusionModule 1000B Maintenance Manual page 57

Air-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
Device
Fire alarm
horn/strobe
VESDA
Issue 02 (2017-01-10)
Operation
Check
Standard
every 6s.
If the smoke
density
exceeds the
alarm
threshold, the
indicator turns
on. The fire
alarm control
panel
generates an
alarm and
triggers the fire
alarm sounder.
Unlock the fire
The fire alarm
alarm control panel
horn/strobe
and press
generates
HORN/STROBE.
glaring flashes
and shrill
alarms.
Check the VESDA
The supports
sampling pipes.
and connectors
of the
sampling pipes
are securely
connected.
Remove or block a
An alarm is
sampling pipe.
generated.
Release smoke to
The VESDA
the furthest end of
generates an
alarm in 120s.
a VESDA
sampling pipe.
The VESDA
panel displays
an alarm.
Check the VESDA
All indicators
operation panel.
are normal.
Check whether the
The backup
backup power is
power is
working properly,
working
and whether the
properly, and
VESDA restarts
the VESDA
normally after the
restarts
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4 Routine Maintenance
Troubleshooting
If the fault persists, replace by
following instructions in
Replacing a Smoke Detector
(Standard).
1. Check cables connected to the
fire alarm control panel. If a
short circuit or open circuit is
identified, reconnect the cables.
2. If the fire alarm horn/strobe does
not react, replace by following
instructions in
6.4.5 Replacing
an External Horn Strobe
(Standard)
or
6.4.4 Replacing an
Indoor Fire Alarm Horn/Strobe
(Standard).
Replace damaged sampling pipes,
and apply glue where pipes are not
well sealed.
See documents delivered with the
VESDA.
See documents delivered with the
VESDA.
See documents delivered with the
VESDA.
See documents delivered with the
VESDA.
See documents delivered with the
VESDA.
6.4.1
49