Maintenance Guide
Step 8 Use a Phillips screwdriver to tighten the screws at the upper and lower parts of the new
emergency start/abort switch.
Step 9 Switch on the active and standby power supplies to the fire alarm control panel.
Step 10 Check that the new emergency start/abort switch is working properly.
----End
Follow-up Procedure
Dispose of the removed emergency start/abort switch that is confirmed faulty.
6.4.8 Replacing Batteries for the Fire Alarm Control Panel
(Standard)
Prerequisites
Impact on the System
None
Preparations
Tools: protective gloves, step ladder, Phillips screwdriver
Materials: spare fire alarm control panel batteries
Documents: fire extinguishing device layout diagram (standard)
Skill requirement: fire engineer
Procedure
Step 1 Switch off the standby power supply to the fire alarm control panel.
Issue 02 (2017-01-10)
If the run indicator of the new emergency start/abort switch is on after power-on, the emergency
start/abort switch is working properly.
Fire alarm control panel batteries need to be replaced.
Spare fire alarm control panel batteries of the same model are available and functional.