Huawei FusionModule 1000B Maintenance Manual page 164

Air-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Air-Cooled IT Solution
Maintenance Guide
Preparations
Tools: protective gloves, step ladder, Phillips screwdriver
Materials: spare smoke detector
Document: fire extinguishing device layout diagram (CE)
Skill requirement: fire engineer
Procedure
Step 1 Disconnect the battery cables, and switch off the input circuit breaker of the extinguishant
control panel.
Step 2 Hold the smoke detector, and rotate it counterclockwise to remove it from the base.
Figure 6-78 Removing a smoke sensor
Step 3 Remove cables from the base using a Phillips screwdriver.
Step 4 Remove the screws on the base using a Phillips screwdriver, and remove the base.
Step 5 Install the new base to the same position, and reconnect the cables.
Step 6 Insert the new smoke detector into the base, and rotate it clockwise until it locks in.
Issue 02 (2017-01-10)
For the diagrams, see the initial configuration parameter manual for the solution in use.
Before replacing the smoke detector, inform the related administration department of the
temporary downtime of the fire control system. After the replacement, inform the
administration department that the system has become operational.
As a terminal resistor is connected to the last smoke detector in the loop in parallel, remove the terminal
resistor from the faulty smoke detector, and connect the resistor to the new smoke detector when you
replace the smoke detector.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Parts Replacement
156

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fusionmodule 1000

Table of Contents