5.3.4 Grounding the ESS
Prerequisites
Do not connect devices such as fuses and switches to ground cables.
The grounding should comply with the local electrical safety regulations.
●
●
Context
The requirements of ground cable are as follows:
Table 5-2 Ground cable description
Cable
Ground cable
The specifications of the ground cable are subject to this table or calculated
according to IEC 60364-5-54.
Connect Ground Cables
Step 1 Connect the main ground bar of the control unit cabin.
● The ground cable of the main ground bar in the control unit cabin must be
● After connecting the ground cable of the main ground bar in the control unit
Issue 15 (2023-11-01)
WARNING
CA UTION
The ESS is installed.
The grounding requirements are clear.
Type
Single-core
outdoor
copper cable
and M10,
M12 OT/DT
terminals
NO TICE
connected.
cabin, close the cabin door in time.
Copyright © Huawei Technologies Co., Ltd.
Cross-
Outer
Sectional
Diameter
Area
2
10–32 mm
16–95 mm