Samsung OfficeServ 7400 Technical Manual page 77

Hide thumbs Also See for OfficeServ 7400:
Table of Contents

Advertisement

OfficeServ 7400
TECHNICAL MANUAL
INSTALLATION PROCEDURE
This section describes how to install OfficeServ 7150 PoE on the floor or inside a rack.
Select an Installation Method
OfficeServ 7150 may be installed either on the floor or inside a 19 inch rack.
1) Ground the system to the grounding lug at the rear side of 7150.
2) Remove the blanking plate from the slot where the POE-M PSU module is to be
inserted.
Do not remove a blanking plate from unused slots.
3) Insert the POE-M module into the slot.
4) Connect an external battery with proper capacity if required.
5) Connect AC input voltage.
INSTALLATION IN A RACK
• Install in a standard 19"data rack.
• If an enclosed rack is used, check if proper ventilation system has been installed in
the rack.
• If an open rack is used, do not to block the front of the OfficeServ 7150 fan.
Tools Required
• One medium size Phillips screw driver
• One cross bar bracket and three screws
• Two rack mount brackets and six screws
• Two fixing screws