Forcing By Using Pcm600 - ABB Relion 670 Series Commissioning Manual

Bay control version 2.2 iec
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 10
Testing IED operation
IEC15000020 V1 EN-US
Figure 22: Example of LHMI menu using BIM3
The signal "freezes" and will not change value even if, for example, a binary input signal voltage
changes level, or if a binary output is activated as the result of a protection function block
activating.
10.8.3.2

Forcing by using PCM600

In PCM600 the concept is a bit different compared to LHMI.The forcing is accomplished by
entering a forcing session. Within such a session, multiple signals on multiple I/O boards may
be edited and changed at the same time and has no effect on the IED. Once the user is
satisfied with the forcing setup, then all the changes can be effectuated simultaneously
towards the IED, potentially changing inputs and outputs on multiple I/O boards at the same
time. It is also possible to abort this operation (described in step 6 below) and to
forcing.
1.
Right click on the IED in the plant structure and select
2.
Click on the
3.
Click
IEC15000023 V1 EN-US
4.
Click
IEC15000024 V1 EN-US
The Signal Monitoring menu changes and indicates the forcing values that can be edited.
88
List View tab.
Forcing Session in the menu IED/Start Forcing .
Start editing signal value for forcing on the tool bar.
© Copyright 2017 ABB. All rights reserved
1MRK 511 403-UEN E
GUID-E9D0DAE6-7A86-4FF9-943E-42039015D05B v2
undo all
Signal Monitoring.
Bay control REC670
Commissioning manual