Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
IEC140000139 V1 EN-US
Figure 11:
•
Open the drop-down menu in the
sent from the client (PMU Connection Tester) to the PMU. Try different commands and
make sure that the PMU is receiving and responding to them.
72
Graphic view over streaming synchrophasor data
Command field. There is a list of commands that can be
© Copyright 2017 ABB. All rights reserved
1MRK 511 403-UEN E
IEC140000139-1-en.vsd
Bay control REC670
Commissioning manual