Verifying The Communication; Verifying The Ieee C37.118/1344 Tcp Communication - ABB Relion 670 Series Commissioning Manual

Bay control version 2.2 iec
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 403-UEN E
9.5

Verifying the communication

Connect your PC to the substation network and ping the connected IED and the Substation
Master PC, to verify that the communication is working (up to the transport layer). Make sure
that the optical fibers are connected correctly.
After checking the communication, it is time to verify the IEEE C37.118/1344 communication
over both TCP and UDP protocols.
One way to verify the communication up to the application layer is to use a protocol analyzer
connected to the substation bus, and monitor the communication. Alternatively, the PMU
Connection Tester tool can be used to verify the IEEE C37.118/1344 communication. The
section
Tester parameters in order to establish an IEEE C37.118 connection with the PMU.
9.5.1

Verifying the IEEE C37.118/1344 TCP communication

After setting both PMU configuration and the TCP client configuration (As explained in
sections
communication (PMU configuration)
making sure that the Ethernet communication is set up, click
Tester tool.
IEC140000138 V1 EN-US
Figure 10: Verifying the TCP communication using PMU Connection Tester
Now it should be possible to see the streaming synchrophasor data. In the Graph tab,
observe the Frequency, data Reporting Rate, Phasor names, and Phase angles of the
reported synchrophasors. Observe the real-time frame details of the Data Frame in the
bottom of the window.
Bay control REC670
Commissioning manual
Setting the TCP/UDP client communication
Setting the PMU station communication (PMU
© Copyright 2017 ABB. All rights reserved
Establishing connection and verifying the IEEE C37.118/1344 communication
explains how to set the PMU Connection
Report),
and
Setting the TCP/UDP client
GUID-D10769FC-6C70-48A3-A1D8-FAFCCA82A3BE v2
GUID-289E2E92-431E-45FE-B586-A723588B98A1 v1
Setting the PMU station
communication) and
Connect on the PMU Connection
IEC140000138-1-en.vsd
Section 9
71

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents