Section 4
Starting up
DHCP is available for the front port, and a device connected to it can thereby obtain an
automatically assigned IP address via the local HMI path Main menu/Configuration/
Communication/Ethernet configuration/Front port/DHCP.
Alternatively the default IP address for the IED front port is 10.1.150.3 and the corresponding
subnetwork mask is 255.255.255.0, which can be set via the local HMI path Main menu/
Configuration/Communication/TCP-IP configuration/ETHFRNT:1Main menu/Configuration/
Communication/Ethernet configuration/AP_FRONT.
Setting up the PC or workstation for point-to-point access to IEDs front
port
An ethernet cable (max 2 m length) with RJ-45 connectors is needed to connect two physical
Ethernet interfaces together without a hub, router, bridge or switch in between.
1.
Select Search programs and files in the Start menu in Windows.
IEC13000057 V1 EN-US
Figure 3:
2.
Type View network connections and click on the View network connections icon.
48
If an IED is equipped with optical LC interface, a converter between RJ-45 and
LC is needed.
Select: Search programs and files
© Copyright 2017 ABB. All rights reserved
IEC13000057-1-en.vsd
Bay control REC670
Commissioning manual
1MRK 511 403-UEN E