ABB Relion 670 Series Commissioning Manual page 69

Bay control version 2.2 iec
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 403-UEN E
The LON communication setting parameters are set via the local HMI. Refer to the Technical
manual for more detailed specifications.
If LON communication from the IED stops because of illegal communication parameter
settings (outside the setting range) or due to other kind of disturbance, it is possible to reset
the IED's LON port.
LON communication setting parameters (Table 16) and LON node information parameters
(Table 17) can only be set via the LON Network Tool (LNT).
Some of these parameters can be viewed on the local HMI under Main menu/Configuration/
Communication/Station communication/Port configuration/SLM optical LON port/
LONGEN:1.
Table 16:
Parameter
DomainID
SubnNetAddr*
NodeAddr*
*Can be viewed on the local HMI
Table 17:
Parameter
NeuronID*
Location
*Can be viewed on the local HMI
ADE settings are available on the local HMI under Main menu/Configuration/Communication/
Station communicaton/LON/ADE:1
Table 18:
Name
Operation
TimerClass
LON commands are available on the local HMI under Main menu/Configuration/
Communication/Station communication/Port configuration/SLM optical LON pot/Service
Pin Messae/Generate service pin message
Table 19:
Command
ServPinMess
Bay control REC670
Commissioning manual
LON communication setting parameters
Range
Default
0
0
0 - 255
0
Step: 1
0 - 127
0
Step: 1
LON node information parameters
Range
Default
0 - 12
Not loaded
0 - 6
No value
ADE Non group settings (basic)
Values (Range)
Unit
Off
On
Slow
Normal
Fast
LON commands
Command description
Command with confirmation. Transfers the node address to the LON Network Tool.
© Copyright 2017 ABB. All rights reserved
Establishing connection and verifying the LON communication
Unit
Parameter description
-
Domain identification number
-
Subnet address
-
Node address
Unit
Parameter description
-
Neuron hardware identification number in
hexadecimal code
-
Location of the node
Step
-
-
-
-
Default
Description
Off
Operation
Slow
Timer class
Section 7
M11888-3 v5
M11643-1 v4
63