Section 7 Administration
Instead of loading the Ghost image it is also possible to delete the
Compact HMI 800 system with the Configuration Wizard and then restore the last
known correct configuration from the backup drive. Note that a restore is not
possible if there are any Compact HMI 800 systems created. It is crucial that the
Configuration Wizard is used when deleting the Compact HMI 800 system.
Deleting the system manually by just removing the files from the hard drive is not
enough.
To use the supplied Ghost software and to restore a Ghost image, a bootable Ghost
CD is required. Use one of the supplied Bootable Ghost CDs.

Backup and Restore of Configuration Data

To backup the configuration data of the system follow the steps below. Note that the
data for the applications that are not integrated in the system, needs to be backed up
separately.
1.
Log on as SysAdmin and open the Plant Explorer.
2.
Select the maintenance structure and expand the object backup definitions.
Select the aspect Backup definition to get the view below.
Figure 71. Plant Explorer Workplace