Main Protection Functions; Back-Up Protection Functions - ABB Relion REC670 Applications Manual

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

Section 2
Application
Forcing of binary inputs and outputs is a convenient way to test wiring in substations as well
as testing configuration logic in the IEDs. Basically it means that all binary inputs and outputs
on the IED I/O modules (BOM, BIM, IOM & SOM) can be forced to arbitrary values.
Central Account Management is an authentication infrastructure that offers a secure solution
for enforcing access control to IEDs and other systems within a substation. This incorporates
management of user accounts, roles and certificates and the distribution of such, a procedure
completely transparent to the user.
Flexible Product Naming allows the customer to use an IED-vendor independent 61850 model
of the IED. This customer model will be used as the IEC 61850 data model, but all other aspects
of the IED will remain unchanged (e.g., names on the local HMI and names in the tools). This
offers significant flexibility to adapt the IED to the customers system and standard solution
2.2

Main protection functions

Table 2:
2
0-3
3-A03
IEC 61850
ANSI
Differential protection
HZPDIF
87
2.3

Back-up protection functions

IEC 61850
ANSI
Current protection
PHPIOC
50
OC4PTOC
1)
51_67
EFPIOC
50N
EF4PTOC
51N
2)
67N
Table continues on next page
30
Example of quantities
= number of basic instances
= option quantities
= optional function included in packages A03 (refer to ordering details)
Function description
1Ph high impedance
differential
protection
Function description
Instantaneous
phase overcurrent
protection
Four step phase
overcurrent
protection
Instantaneous
residual overcurrent
protection
Four step residual
overcurrent
protection
Bay control
REC670
(Customized)
0-6
3-A02
Bay control
REC670
(Customized)
0-6
1-C51
0-6
1-C51
0-6
1-C51
0-6
1-C51
1MRK 511 358-UEN A
GUID-66BAAD98-851D-4AAC-B386-B38B57718BD2 v12.1.1
3-A02
3-A02
6-A07
GUID-A8D0852F-807F-4442-8730-E44808E194F0 v10
1-C51
2-C52
2-C53
1-C51
2-C52
2-C53
1-C51
2-C52
2-C53
1-C51
2-C52
2-C53
Application manual