Section 11 System Protection And Control; Multipurpose Filter Smaihpac; Identification; Application - ABB Relion REC670 Applications Manual

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

1MRK 511 358-UEN A
Section 11
11.1

Multipurpose filter SMAIHPAC

11.1.1

Identification

Function description
Multipurpose filter
11.1.2

Application

The multi-purpose filter, function block with name SMAI HPAC, is arranged as a three-phase
filter. It has very much the same user interface (e.g. function block outputs) as the standard
pre-processing function block SMAI. However the main difference is that it can be used to
extract any frequency component from the input signal. For all four analogue input signals into
this filter (i.e. three phases and the residual quantity) the input samples from the TRM module,
which are coming at rate of 20 samples per fundamental system cycle, are first stored. When
enough samples are available in the internal memory, the phasor values at set frequency
defined by the setting parameter
internally available for each of the calculated phasors:
Magnitude
Phase angle
Exact frequency of the extracted signal
The SMAI HPAC filter is always used in conjunction with some other protection function (e.g.
multi-purpose protection function or overcurrent function or over-voltage function or over-
power function). In this way many different protection applications can be arranged. For
example the following protection, monitoring or measurement features can be realized:
Sub-synchronous resonance protection for turbo generators
Sub-synchronous protection for wind turbines/wind farms
Detection of sub-synchronous oscillation between HVDC links and synchronous
generators
Super-synchronous protection
Detection of presence of the geo-magnetic induced currents
Overcurrent or overvoltage protection at specific frequency harmonic, sub-harmonic,
inter-harmonic etc.
Presence of special railway frequencies (e.g. 16.7Hz or 25Hz) in the three-phase power
system
Sensitive reverse power protection
Stator or rotor earth fault protection for special injection frequencies (e.g. 25Hz)
etc.
The filter output can also be connected to the measurement function blocks such as CVMMXN
(Measurements), CMMXU (Phase current measurement), VMMXU (Phase-phase voltage
measurement), etc. in order to report the extracted phasor values to the supervisory system
(e.g. MicroSCADA).
Application manual
System protection and control
IEC 61850
identification
SMAIHPAC
SetFrequency are calculated. The following values are
System protection and control
GUID-6B541154-D56B-452F-B143-4C2A1B2D3A1F v1