Scheme Communication Logic For Residual Overcurrent Protection Ecpsch; Identification; Application - ABB Relion REC670 Applications Manual

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

1MRK 511 358-UEN A
LoadCurr
EQUATION1320 V1 EN-US
where:
ILoadmin is the minimum load current on the line during normal operation conditions.
The timer
avoid unwanted release due to transient inrush current when energizing the line power
transformer. The loss-of-load function will be released after the timer
the same time as the load current in all three phases are above the setting
acceleration applications there is no need for delaying the release, so set the
The drop-out timer
conditions for Loss-of-load. The timer is by default set to 300ms, which is judged to be
enough to secure the current release.
The setting of the minimum current detector,
unsymmetrical current that might flow on the non faulty line, when the breaker at remote end
has opened (three-phase). At the same time it should be set below the minimum load current
transfer during normal operations that the line can be subjected to. By default,
to 5% of
The pick-up timer
value used to release the function. The timer is by default set to 200 ms, which is judged to be
enough to avoid unwanted release of the function (avoid unwanted trip).
14.4
Scheme communication logic for residual overcurrent
protection ECPSCH
14.4.1

Identification

Function description
Scheme communication logic for
residual overcurrent protection
14.4.2

Application

To achieve fast fault clearance of earth faults on the part of the line not covered by the
instantaneous step of the residual overcurrent protection, the directional residual overcurrent
protection can be supported with a logic that uses communication channels.
One communication channel is used in each direction, which can transmit an on/off signal if
required. The performance and security of this function is directly related to the transmission
channel speed and security against false or lost signals.
In the directional scheme, information of the fault current direction must be transmitted to
the other line end.
Application manual
×
0.5
I
Load
min
=
I
Base
tLoadOn is used to increase the security of the loss-of-load function for example to
tLoadOff is used to determine the window for the current release
IBase .
tLowCurr determine the window needed for pick-up of the minimum current
MinCurr , should be set higher than the
IEC 61850
IEC 60617
identification
identification
ECPSCH
-
Section 14
Scheme communication
(Equation 130)
tLoadOn has elapsed at
LoadCurr . In normal
tLoadOn to zero.
MinCurr is set
ANSI/IEEE C37.2
device number
85
IP14711-1 v2
M14882-1 v2
M13919-3 v5
351