ABB Relion REC670 Applications Manual page 115

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

1MRK 511 358-UEN A
Operate time
tx
txMin
IEC10000058 V2 EN-US
Figure 44: Minimum operate current and operate time for inverse time characteristics
In order to fully comply with the definition of the curve, the setting parameter
set to a value equal to the operating time of the selected inverse curve for twenty times the set
current pickup value. Note that the operate time is dependent on the selected time multiplier
setting
ResetTypeCrvx : The reset of the delay timer can be made as shown in Table 15.
Table 15:
Curve name
Instantaneous
IEC Reset (constant time)
ANSI Reset (inverse time)
The delay characteristics are described in
regarding the choice of the reset delay.
For the definite time delay characteristics, the possible delay time setting instantaneous (1)
and IEC (2 = set constant time reset).
For ANSI inverse time characteristics, all three types of reset time characteristics are available:
instantaneous (1), IEC (2 = set constant time reset) and ANSI (3 = current dependent reset
time).
For IEC inverse time characteristics, the possible delay time settings are instantaneous (1) and
IEC (2 = set constant time reset).
For the customer tailor-made inverse time delay characteristics (type 17), all three types of
reset time characteristics are available: instantaneous (1), IEC (2 = set constant time reset) and
ANSI (3 = current dependent reset time). If the current-dependent type is used, settings
cr must be given.
and
tResetx : Constant reset time delay in seconds for step x.
tPCrvx , tACrvx , tBCrvx , tCCrvx : These parameters are used by the customer to create the
inverse time characteristic curve. See equation
more information, refer to
Application manual
IMinx
kx .
Reset possibilities
Technical manual .
Current
IEC10000058
Curve index no.
1
2
3
Technical manual . There are some restrictions
28
for the time characteristic equation. For
Section 7
Current protection
txMin shall be
pr , tr
109