Section 13
Control
IEC05000120 V2 EN-US
Figure 110: Example overview of the interactions between functions in a typical bay
13.3.3

Setting guidelines

The setting parameters for the apparatus control function are set via the local HMI or PCM600.
13.3.3.1

Bay control (QCBAY)

If the parameter
accepted without any priority.
If the parameter
station and remote level are accepted, when the QCBAY function is in Remote. If set to
command LocSta controls which operator place is accepted when QCBAY is in Remote. If
264
SMPPTRC
(Trip logic)
QCBAY
Operator place
(Bay control)
selection
Res. req.
Res. granted
QCRSV
(Reservation)
Res. req.
Close CB
SMBRREC
(Auto-
reclosure)
Open rel.
Interlocking
Close rel.
function
Open rel.
block
Close rel.
(Not a LN)
Position
Res.
GAPC
granted
(Generic
Automatic
Open/Close
Process
Control)
Open/Close
AllPSTOValid is set to No priority , all originators from local and remote are
RemoteIncStation is set to Yes , commands from IEC61850-8-1 clients at both
SESRSYN
(Synchrocheck & Synchronizer)
Trip
Synchrocheck
OK
Open cmd
Close cmd
SCSWI
(Switching control)
Position
SCILO
(Interlocking)
SCILO
(Interlocking)
Enable
Enable
open
close
Open cmd
Close cmd
SCSWI
(Switching control)
Position
1MRK 511 358-UEN A
Synchronizing
in progress
SXCBR
(Circuit breaker)
I/O
SXSWI
(Disconnector)
I/O
IEC05000120-2-en.vsd
No , the
Application manual
M16669-3 v4
M16670-3 v6