ABB Relion REC670 Applications Manual page 119

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

1MRK 511 358-UEN A
IEC05000204 V1 EN-US
Figure 46: Fault time with maintained selectivity
The operation time can be set individually for each overcurrent protection.
To assure selectivity between different protections, in the radial network, there have to be a
minimum time difference Dt between the time delays of two protections. The minimum time
difference can be determined for different cases. To determine the shortest possible time
difference, the operation time of protections, breaker opening time and protection resetting
time must be known. These time delays can vary significantly between different protective
equipment. The following time delays can be estimated:
Protection operation
time:
Protection resetting
time:
Breaker opening time:
Example for time coordination
Assume two substations A and B directly connected to each other via one line, as shown in the
figure 47. Consider a fault located at another line from the station B. The fault current to the
overcurrent protection of IED B1 has a magnitude so that the protection will have
instantaneous function. The overcurrent protection of IED A1 must have a delayed function.
The sequence of events during the fault can be described using a time axis, see figure 47.
Application manual
15-60 ms
15-60 ms
20-120 ms
Current protection
en05000204.wmf
Section 7
113

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents