Section 15
Logic
15.13.4
Setting example
For absolute comparison between inputs:
Set the
Set the
Similarly for Signed comparison between inputs
Set the
Set the
For absolute comparison between input and setting
Set the
Set the
SetValue shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
Set the
Set the
SetValue shall be set between -2000000000 to 2000000000.
15.14
Comparator for real inputs - REALCOMP
15.14.1
Identification
Function description
Comparator for real inputs
15.14.2
Application
The function gives the possibility to monitor the level of real values in the system relative to
each other or to a fixed value. It is a basic arithmetic function that can be used for monitoring,
supervision, interlocking and other logics.
15.14.3
Setting guidelines
Setting procedure on the IED:
EnaAbs : This setting is used to select the comparison type between signed and absolute
values.
Absolute : The function will do absolute comparison between input and reference value.
•
Signed : The function will do signed comparison between input and reference value.
•
372
EnaAbs = 1
RefSource = 1
EnaAbs = 0
RefSource = 1
EnaAbs = 1
RefSource = 0
EnaAbs = 0
RefSource = 0