Current Transformers According To Ansi/Ieee; Voltage Transformer Requirements - ABB Relion REC670 Applications Manual

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

1MRK 511 358-UEN A
»
E
knee
EQUATION2100 V2 EN-US
22.1.7.3

Current transformers according to ANSI/IEEE

Current transformers according to ANSI/IEEE are partly specified in different ways. A rated
secondary terminal voltage U
terminal voltage the CT will deliver to a standard burden at 20 times rated secondary current
without exceeding 10 % ratio correction. There are a number of standardized U
example, U
e.m.f. E
E
alANSI
EQUATION971 V2 EN-US
where:
Z
bANSI
U
ANSI
The CTs according to class C must have a calculated rated equivalent limiting secondary e.m.f.
E
that fulfils the following:
alANSI
E
alANSI
EQUATION1384 V2 EN-US
A CT according to ANSI/IEEE is also specified by the knee point voltage U
graphically defined from an excitation curve. The knee point voltage U
lower value than the knee-point e.m.f. according to IEC and BS. U
estimated to 75 % of the corresponding E
according to ANSI/IEEE must have a knee point voltage U
V
kneeANSI
EQUATION2101 V2 EN-US
22.2

Voltage transformer requirements

The performance of a protection function will depend on the quality of the measured input
signal. Transients caused by capacitive voltage transformers (CVTs) can affect some
protection functions.
Magnetic or capacitive voltage transformers can be used.
The capacitive voltage transformers (CVTs) should fulfill the requirements according to the IEC
61869-5 standard regarding ferro-resonance and transients. The ferro-resonance
requirements of the CVTs are specified in chapter 6.502 of the standard.
Application manual
(
»
»
>
×
E
E
U
0.8 maximum of E
k
kneeBS
al
ANSI
is 400 V for a C400 CT. A corresponding rated equivalent limiting secondary
ANSI
can be estimated as follows:
alANSI
=
×
×
+
20 I
R
U
sr
ct
ANSI
The impedance (that is, with a complex quantity) of the standard ANSI burden for the specific C class
(W)
The secondary terminal voltage for the specific C class (V)
>
maximum of E
alreq
>
×
0.75 (max imum of E
)
alreq
is specified for a CT of class C. U
=
×
×
+
×
20 I
R
20 I
sr
ct
sr
according to IEC 61869-2. Therefore, the CTs
al
)
alreq
is the secondary
ANSI
ANSI
×
Z
bANSI
kneeANSI
normally has a
kneeANSI
can approximately be
kneeANSI
that fulfills the following:
kneeANSI
Section 22
Requirements
(Equation 137)
M11623-22 v6
values for
(Equation 138)
(Equation 139)
that is
(Equation 140)
M11608-3 v5
463