Instantaneous Residual Overcurrent Protection Efpioc - ABB Relion REC670 Applications Manual

Bay control version 2.1 iec
Hide thumbs Also See for Relion REC670:
Table of Contents

Advertisement

Section 7
Current protection
t=0
The fault
occurs
IEC05000205 V1 EN-US
Figure 47: Sequence of events during fault
where:
t=0
t=t
1
t=t
2
t=t
3
To ensure that the overcurrent protection at IED A1, is selective to the overcurrent protection
at IED B1, the minimum time difference must be larger than the time t
in the values of protection operation time, breaker opening time and protection resetting
time. Therefore a safety margin has to be included. With normal values the needed time
difference can be calculated according to equation 33.
D ³
t
40
EQUATION1266 V1 EN-US
where it is considered that:
the operate time of overcurrent protection B1 is 40 ms
the breaker open time
the resetting time of protection A1
the additional margin
7.3

Instantaneous residual overcurrent protection EFPIOC

114
A1
I>
t=t
t=t
1
Protection
Breaker at
B1 trips
B1 opens
is when the fault occurs
is when the trip signal from the overcurrent protection at IED B1 is sent to the circuit breaker. The
operation time of this protection is t
is when the circuit breaker at IED B1 opens. The circuit breaker opening time is t
is when the overcurrent protection at IED A1 resets. The protection resetting time is t
+
+
+
ms
100
ms
40
ms
B1
I>
t=t
2
3
Protection
A1 resets
1
=
40
ms
220
ms
is 100 ms
is 40 ms and
is 40 ms
1MRK 511 358-UEN A
Feeder
Time axis
en05000205.vsd
- t
2
1
- t
.
3
2
. There are uncertainties
3
(Equation 33)
IP14508-1 v3
Application manual