Conversion

BOOL_TO_DINT
(10018)
Illustration
Execution time
Operation
Standard function blocks
13.47 µs
The output (OUT) value is a 32-bit integer value formed from the boolean input
(IN1...IN31 and SIGN) values. IN1 = bit 0 and IN31 = bit 30.
Example:
IN1 = 1, IN2 = 0, IN3...IN31 = 1, SIGN = 1
OUT = 1111 1111 1111 1111 1111 1111 1111 1101
IN31...IN1