102
13.03 AI1 MIN
Defines the minimum value for analogue input AI1. The type is selected with jumper J1 on the JCU
Control Unit.
-11...11 V / -22...22 mA
13.04 AI1 MAX SCALE
Defines the real value that corresponds to the maximum analogue input value defined by parameter
13.02 AI1
-32768...32768
13.05 AI1 MIN SCALE
Defines the real value that corresponds to the minimum analogue input value defined by parameter
13.03 AI1
-32768...32768
Firmware block:

AI2

(13)
Filters and scales the analogue input
AI2 signal and selects the AI2
supervision. Also shows the value of
the input.
Block outputs located in other
parameter groups
13.06 AI2 FILT TIME
Defines the filter time constant for analogue input AI2. See parameter
0...30 s
Parameters and firmware blocks
MAX.
AI (scaled)
13.04
13.03
13.05
MIN. See parameter
FW block:
AI1
(see above)
Minimum AI1 input value.
FW block:
AI1
(see above)
13.02
AI (mA / V)
Real value corresponding to value of parameter 13.02.
FW block:
AI1
(see above)
13.04 AI1 MAX
SCALE.
Real value corresponding to value of parameter 13.03.
2.06 AI2
(page 68)
2.07 AI2 SCALED
(page 68)
FW block:
AI2
(see above)
Filter time constant for AI2.
AI2
13.01 AI1 FILT
TIME.