Section 3 CCF Displays
3BUR002418-600 A
Table 3. Buttons and Indicators
Icon
Name
Auto
Manual
Computer Mode
Local Mode
Remote
Local
Description
Switch to Auto from Manual. In auto, the
setpoint and ratio can be adjusted. If shaded,
switching to Auto is not allowed.
Switch to Manual from Auto. In manual, the
output can be adjusted. If shaded, switching
to Manual is not allowed.
Request a switch to Computer mode.
Restricted parameters for PID loops are
SETPOINT, SPT_MODE, RESULT and
OUT_MODE. Restricted parameters for
Controller loops are RESULT and
OUT_MODE.
In Computer Mode, you have two options;
LOCAL, where the operator is able to access
the restricted parameters but the computer
cannot, and COMPUTER, where the
computer program is allowed access to the
restricted parameters but the operator is not.
When the COMPUTER option is selected, the
operator can still change control to LOCAL.
In Local Mode, the operator is able to access
the restricted parameters but the computer
cannot (see Computer Mode).
Switch to remote setpoint. Remote setpoint
value is the result of another FCM. If shaded,
switching to Remote is not allowed.
Switch to local setpoint. Local setpoint value
comes from within the PID FCM. The operator
can change this value. If shaded, switching to
Local is not allowed.
Operator Controls
43