Do810 - ABB 800xA Operation

For mod 300
Hide thumbs Also See for 800xA:
Table of Contents

Advertisement

Appendix A Runtime Templates
RESERVED OPTIONS
This field reserved for future use. A zero (0) should be entered as a default value.
VALUE CYCLE TIME
Enter the channel value update period (msec) over the fieldbus. Refer to S800 I/O
User's Guide for details of AF 100 loading in relation to cycle time.
The valid values are:
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048 and 4096.
The default value is 128.

DO810

The DO810 templet is also used for the DO890 except as noted in the field entry
descriptions. The DO890 also supports only 4 channels.
ACTIVE 01 through 16
If the channel is to be active enter a YES.
If the channel will not be used enter a NO.
The default value is YES.
AUTO DOWNLOAD
To automatically download the configuration to the I/O module enter a YES. In the
future, if the configuration is to be loaded locally enter a NO.
Default value is YES.
CLUSTER
Enter the I/O device cluster of the station where this module is located. The cluster
connected directly to the FCI is number zero (0). The number in this field is 0 -7.
Default value is 0.
3BUR002418-600 A
DO810
309