Do814 - ABB 800xA Operation

For mod 300
Hide thumbs Also See for 800xA:
Table of Contents

Advertisement

Appendix A Runtime Templates
The default value is 128.

DO814

ACTIVE 01 through 16
If the channel is to be active enter a YES.
If the channel will not be used enter a NO.
The default value is YES.
AUTO DOWNLOAD
To automatically download the configuration to the I/O module enter a YES. In the
future, if the configuration is to be loaded locally enter a NO.
Default value is YES.
CLUSTER
Enter the I/O device cluster of the station where this module is located. The cluster
connected directly to the FCI is number zero (0). The number in this field is 0 -7.
Default value is 0.
DQ CYCLE TIME
Enter the channel data quality update period (msec) over the fieldbus. Refer to the
S800 I/O User's Guide for details of AF 100 loading in relation to cycle time.
The valid values are:
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048, and 4096
The default value is 128.
LABEL
Enter a characteristic name to identify the DO814 Module of the station. The name
may contain up to 20 characters.
3BUR002418-600 A
DO814
313

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents