Real Compare Fcm - ABB 800xA Operation

For mod 300
Hide thumbs Also See for 800xA:
Table of Contents

Advertisement

Real Compare FCM

where
prev is the value of the result from the previous sample period
any non-zero input is treated as a 1
As long as inp2 (Reset) is 0, the result goes to 1 as soon as inp1 (Set) goes to 1. The
result remains at 1 regardless of the subsequent state of inp1. When inp2 goes to 1,
the result is forced to 0, and remains there as long as inp2 is 1.
Real Compare FCM
This FCM compares two analog signals and provides a logical output if a specified
condition is met.
COMPENSATION CONSTANT Field
This field specifies the comparison constant, when INPUT SOURCE 2 is not
specified. Valid entry is any number.
COMPARE OPERATOR Field
This field specifies the operator for the comparison constant. Valid entries are:
NORMAL STATE Field
This field specifies the normal state of the FCM's result. Valid entries are: 0, 1
272
0
1
1
EQ
equal to
NE
not equal to
GT
greater than
GE
greater than or equal to
LT
less than
LE
less than or equal to
1
0
0
1
1
0