Appendix A Runtime Templates
OSP VALUE 01 through 08
Enter the channel value (0 or 1) to output after an OSP TIMEOUT. If the OSP
HOLD has been selected as the OSP value then this field entry is ignored.
The valid values are:
0 or 1.
Where 0 = off and 1 = on.
The default is 0.
POSITION
Enter a number from 1 to 12 representing the position of the I/O module relative to
the FCI. The I/O module directly next to the FCI is number 1.
Default value is 1.
REPORT FAULTS 01 through 08
If channel faults are to be reported, enter a YES;
if not enter a NO.
The default value is YES.
RESERVED OPTIONS
This field reserved for future use. A zero (0) should be entered as a default value.
VALUE CYCLE TIME
Enter the channel value update period (msec) over the fieldbus. Refer to S800 I/O
User's Guide for details of AF 100 loading in relation to cycle time.
The valid values are:
1, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024, 2048 and 4096.
The default value is 128.
3BUR002418-600 A
DO820
317