Section 7 I/O Displays
If the station is the CI520/CI522 type CTL, selecting that station icon will bring up
the CI520/CI522 Diagnostics Display,
Figure 68. CI520/CI522 Diagnostics Display
3BUR002418-600 A
15
STN
A
B
tz3_l3_s15
HRY STN 15
Station Item
Station
This is the number of the S800 I/O
Number
Station as specified during database
configuration (1 - 80). It is also a screen
target to the Station display.
Station Type
The station type is shown under the
station number. STN = I/O Station, CTL
= Controller (CI520/CI522) and UNK =
unknown.
Status Boxes
This shows a letter for station status.
M = missing, F = failed, U = unknown, N
= not ready, R = ready, A = active and B
= backup.
Station Border Border color is based on the letter
shown in the status box. M, F and U =
red, N = orange, B and R = yellow and
A = green. Border will flash when
diagnostic messages are present.
Templet Name
Displayed as a single line tool tip when
and Label
the cursor is over the station target. The
templet name is first and label is
second.
Figure
68.
S800 LAN Display
Description