5.4.4.1
1) If the transceiver does not feature a Sleep mode and receives power
2) If the transceiver features a Sleep mode or is continuously powered,

5.4.5 Transceiver check

5.4.5.1
1) If available, use a wattmeter to check the transceiver output power. Refer to
2) If available, use two hand-held transceivers, and verify the communication
3) Verify that the transceiver is set to the correct frequency. Refer to the
4) If a directional antenna is used, verify the orientation to the antennae to the

5.4.6 Termination board supply voltage test

1) Using a DMM set to Volts DC, measure the power supply voltage from the
2) If the supplied voltage falls in the correct range, return to the test sequence
2104349 rev. AD
Step-by-step instructions
through an optional relay, activate COM1SW or COM2SW, and using a
Digital Multi-meter (DMM) set to Volts DC, measure the voltage at the relay
between the relay coil terminals.
If the voltage reads the same as the supplied voltage (12 VDC) and the
transceiver is still not receiving power, the relay may be incorrectly wired
(use normally open contacts), or the relay may be bad.
If the relay is not receiving power, continue to step 2.
activate COMSW1 or COM2SW, and using a DMM set to Volts DC,
measure the voltage at the next supply junction. If the next junction is
located on the termination strip, verify the wiring is firmly connected;
otherwise, continue to the charger relay, and measure the voltage between:
Terminal 1 (Batt +) and Terminal 4 (Batt -)
Voltage should be greater than or equal to 11.9 VDC for this unit. If the
voltage is less than 11.9, return to the test sequence outlined in the Power
Troubleshooting section.
Step-by-step instructions
the manufacturer's documentation for measuring instructions.
path between the master and remote sites. Voice-activated interface can be
used, if available.
manufacturer's documentation for checking the frequency instructions.
master site.
If a communication problem still exists and the unit has
passed the transceiver check test, contact Totalflow
Technical Support for additional help.
OEU enclosure to J16 on the termination board (see Figure 5–4) between:
Voltage should be equal to or greater than the amount specified as low
voltage input in PCCU32 for this unit (9 volt minimum, default is 11.9 VDC).
outlined in the Power Troubleshooting section.
Pin 1 (+) and Pin 2 (-)
Page 5–17