The Current Value parameter will display the current value of the selected RTD by
placing a check mark in the Update field.

4.16.1 Step-by-step instructions

1) Connect the variable resistor or RTD calibration equipment to J7 on the G4
2) Select the RTD tab within the Analog Inputs tab sub-menu under Onboard
3) Select whether to perform a 3 Point, 5 Point or Bias calibration. Note that if
2104349 rev. AD
Figure 4–13 RTD calibration screen
EX board.
Terminal
1
2
3
4
5
If the user elects to calibrate using an 100 OHM RTD probe,
refer to the PCCU32 Help Files to view resistance and
corresponding temperature readings.
I/O in the Calibration window.
a 3 Point is selected, there will be 3 Target values and 3 Cal Point buttons.
If 5 Point is selected, there will be 5 Target values and 5 Cal Point buttons.
J7
SHLD
Out
Plus (+)
Minus (-)
In
Page 4–29