Earth Fault Trip Time 0.1; Earth Fault Out 0; Too Long Curr Lim Trip Time 1; Too Long Curr Lim Out 0 - ABB PSTX30 Installation And Commissioning Manual

Hide thumbs Also See for PSTX30:
Table of Contents

Advertisement

7.15.16 Earth fault protection
Programmable digital input can be used in combination
with external device/sensor to provide the possibility of
handling their own defined protection.
This protection detects if the absolute value of the sum
of the three line currents is too high, which indicates that
there is an earth fault.
Note that the currents measurements in the softstarter is
not accurate or fast enough to protect people. The only
purpose of this function is to protected equipment.
Earth fault protection is configured with the following
parameters:
Parameter
18.05 Earth fault trip time
18.06 Earth fault out
18.07 Earth fault op
7.15.17 Too long current limit protection
This protection detacts if the current limit has exceeded
the set value.
The starting condition is too heavy for
the set current limit. Check starting conditions and
parameters.
Too long current limit protection is configured with the
following parameters:
Parameter
18.08 Too long curr lim trip time
18.09 Too long curr lim out
18.10 Too long curr lim op
7.15.18 HMI failure protection
This protection detacts if there is communication
disturbance between the softstarter and the HMI.
If the communication with the HMI is lost for more than
approximatlely 600 ms this protection is activated.
This protection has a special action in addition to the
common types of operation:
Switch to I/O-control.
HMI failure protection is configured with the following
parameters:
Parameter
19.01 HMI failure out
19.02 HMI failure op
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Sets the trip time for the earth fault
protection.
Specifies the Event groups this
protection belongs to.
Sets the operation of this protection. Off, Stop manual,
Description
Sets the trip time for the too long
time at current limit protection.
Specifies the Event groups this
protection belongs to.
Sets the operation of this protection. Off, Stop manual,
Description
Specifies the Event groups this
protection belongs to.
Sets the operation of this protection. Off, Stop manual,
Setting range
Default value
0.1 ... 1.0 s
0.5 s
Eventgroup 0 ... 6
2

Off

Stop auto, Indication.
Setting range
Default value
1 ... 600 s
10 s
Eventgroup 0 ... 6
2
Off
Stop auto, Indication.
Setting range
Default value
Eventgroup 0 ... 6
2
Off
Stop auto, Indication.
7