7.12.2
Relay outputs
The softstarter is equipped with three relay outputs for a
configurable output signal depending of selected function.
The relay outputs are, K4, K5 and K6. The relays outputs
are; 30VDC/250VAC Ith = 5A , Ie= 1,5Amp (AC-15).
The relay opens and closes depending on set
configurations.
All relay outputs are programmable.
Functions or an event group can be related to the physical
signal through a drop down menu on the HMI.
The programmable options for each relays are:
None – No function on the relay outpt.
Run – Indicates when the softstarter gives voltage to
the motor.
Top of ramp (TOR) – Indicates that motor runs on full
voltage.
Event group (0-6) – Faults, protections, warning are
all selectable by customer.
Sequence 1-3 Run – TBD
Sequence 1-3 TOR – TBD
Run reverse – TBD
As default K4 is configured to function Run, K5 to Top of
ramp and K6 to Eventgroup 0.
Description of the relay terminals
7
Each relay has three terminals, one common terminal
(COM), one normally open terminal (NO) and one normally
closed terminal (NC). See Figure 84.
Common – TBD
Normally open – Circuit is open in normal mode (circuit
is not shorted to common).
Normally closed – Circuit is in normal mode (the circuit
is continuously shorted to common).
Internal relay outputs (internal IO)
the following parameters:
Parameter
10.04 K4 function
10.05 K5 function
10.06 K6 function
External relay outputs (extension IO)
with the following parameters:
Parameter
11.09 1DO0 function
11.10 1DO1 function
11.11 2DO2 function
11.12 2DO3 function
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
is configured with
Description
Function of programmable output relay K4.
K5,K6.
Same as K4 function
Same as K4 function
is configured
Description
Function of programmable output relay
1DO0 (extention IO).
Same as 1DO0
Same as 1DO0
Same as 1DO0
84
Common
230V
Contactor
Figure 84:
A contacor may for example be connected (230 volts)
Setting range
None, Reset, Enable, Slow speed
forward, Slow speed backward,
Motor heating, Stand still brake,
Start reverse, User defined
protection, Emergency mode,
Fieldbus disable control, Start 1,
Start 2, Start 3
Same as K4 function
Same as K4 function
Setting range
None, Reset, Enable, Slow speed
forward, Slow speed backward,
Motor heating, Stand still brake,
Start reverse, User defined
protection, Emergency mode,
Fieldbus disable control, Start 1,
Start 2, Start 3
Same as 1DO0
Same as 1DO0
Same as 1DO0
Normally
Normally
Closed
open
Default value
Run
Top of ramp
Event group 0
Default value
Run
Top of ramp
Event group 0
Motor Current (A)