7.7
Kick start
Kick start function is a function to kick loose the motor
initial friction during a set time and level.
If Kick start is enabled, the start ramp starts directly after
Kick start. See figure 83.
INFORMATION
Current limit function will not work during kick
start.
Kick start
is configured with the following parameters:
Parameter
04.01 Kick start
04.02 Kick start level
04.03 Kick start time
7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Enables a voltage peak at the beginning of the start ramp.
Sets the level of the Kick start in percentage of rated voltage.
Sets the duration of the Kick start in seconds.
83
U
Kick Start level
Kick Start time
Figure 83:
Kick start
Setting range
On, Off
50 ... 100 %
0.20 ... 2.00 s
Time
Default value
Off
70 %
0.20 s