7.21 Complete parameter list
Parameter
Description
number
01
Motor rated current Ie
01.01
Motor rated current Ie
02
Start and stop
02.01
Start mode
02.02
Stop mode
02.03
Start ramp initial level
02.04
Start ramp time
02.05
Stop ramp end level
02.06
Stop ramp time
02.07
Pre-start function
02.08
Pre-start time
03
Limit
03.01
Current limit type
03.02
Current limit level
03.03
2nd curr lim level
03.04
2nd curr lim time
03.05
Torque limit level
04
Kick start
04.01
Kick start
04.02
Kick start level
7
04.03
Kick start time
05
Slow speed
05.01
Slow speed forward
05.02
Slow speed fwd strenght
05.03
Slow speed reverse
05.04
Slow speed rev strength
06
Motor heating
06.01
Motor heating capacity
07
Motor braking
07.01
Stand still brake strength
08
Sequence start
08.01
Sequence mode
08.02
Ie seq 1
08.03
Start mode seq 1
08.04
Start ramp time seq 1
08.05
Start ramp init lvl seq 1
08.06
Curr lim level seq 1
08.07
Kick start seq 1
08.08
Kick start level seq 1
08.09
Kick start time seq 1
08.10
Torque lim lvl seq 1
08.11
Torque tune seq 1
08.12
Torque ctrl gain seq 1
08.30
Ie seq 2
08.31
Start mode seq 2
08.32
Start ramp time seq 2
08.33
Start ramp init lvl seq 2
08.34
Curr lim level seq 2
08.35
Kick start seq 2
08.36
Kick start level seq 2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Setting range
9.0 ... 1250.0 A
Voltage ramp, Torque ramp, Full voltage start
No ramp, Voltage ramp, Torque ramp
10 ... 99 %
1 ... 120 s
10 ... 99 %
1 ... 120 s
Pre start off, Motor heating, Stand still brake
Slow speed forward, Slow speed reverse
0.0 ... 7200.0 s
Off, Normal, Dual, Ramp
1.5 ... 7.5 x I e
0.5 ... 7.5 x I e
2 ... 120 s
20 ... 200 %
On / Off
50 ... 100 %
0.2 ... 2.0 s
Fast jog, Jog, Creep
10 ... 100 %
Fast jog, Jog, Creep
10 ... 100 %
10 ... 100000 W
10 ... 100
On / Off
9.0 ... 1250.0 A
Voltage ramp, Torque ramp, Full voltage start
1 ... 120 s
10 ... 99 %
0.5 ... 7.5 x I e
On / Off
50 ... 100 %
0.20 ... 2.0 s
20 ... 200 %
0 ... 1000 %
0.01 ... 10.0
9.0 ... 1250.0 A
Voltage ramp, Torque ramp, Full voltage start
1 ... 120 s
10 ... 99 %
0.5 ... 7.5 x I e
On / Off
50 ... 100 %
Number of
Fieldbus
Default value
decimal
ID
1
1
9.0 A
0
2
Voltage ramp
0
3
No ramp
0
4
30 %
0
5
10 s
0
6
30 %
0
7
10 s
0
0
Pre start off
1
0
10.0 s
0
18
Off
1
19
4.0 x I e
1
20
7.0 x I e
0
21
8 s
0
0
150 %
0
22
Off
0
23
70 %
2
24
0.2 s
0
0
Jog
0
0
50 %
0
0
Jog
0
0
50 %
0
0
10 W
0
0
50 %
0
8
Off
1
0
9.0 A
0
0
Voltage ramp
0
0
10 s
0
0
30 %
1
0
7.0 x I e
0
0
Off
0
0
70 %
2
0
0.20 s
0
0
150 %
0
0
100 %
2
0
0.02
1
0
9.0 A
0
0
Voltage ramp
0
0
10 s
0
0
30 %
1
0
7.0 x I e
0
0
Off
0
0
70 %
Actual