Eol Level 40.0; Eol Out 0; Locked Rotor Level 0.2; Locked Rotor Init Time 1.0 - ABB PSTX30 Installation And Commissioning Manual

Hide thumbs Also See for PSTX30:
Table of Contents

Advertisement

7.16 Warnings
The softstarter is equipped with a number of warning
functions to signal malfunctioning or other potential risks,
before asserting the protection or fault. The difference
between a warning and a protection is that a warning
cannot stop the softstarter and a reset of a warning is
not necessary.The warning level and any other additional
information needed to enable the warning can be set by
the user.
A warning will be logged in the event list when it occurs.
Warnings can be Enable or Disable. There is also a
percentage setting were the user can set at which
percentage level the warning shall occur. The percentage
setting is within 10 - 80 %.
Warnings can be set to an Event group by a parameter
option called Out. The Event group can be configured for
relay output to control other devices in an application.
As default, all parameters are set to one Eventgroup.
Warnings are displayed on the HMI, but otherwise they do
not affect the behaviour of the softstarter.
7.16.1
Electronic overload warning
A warning signal will be given if the motor temperature
exceeds the settable warning level, % of max
temperature.
Electronic overload warning
is configured with the following parameters:
Parameter
20.01 EOL level
20.02 EOL out
23.03 EOL warning
7.16.2
Locked rotor warning
A warning signal will be given if the current exceeds the
settable warning level.
The motor is running stiff. A damaged bearing or a stuck
load could be possible causes. Check the load and the
motor.
Locked rotor warning is configured with the following
parameters:
Parameter
20.04 Locked rotor level
20.05 Locked rotor init time
20.06 Locked rotor out
20.07 Locked rotor
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
Sets the EOL warning level.
Specifies the Event groups this
warning belongs to.
Enables EOL warning.
Description
Sets the Locked rotor warning level.
Sets the time delay after top of
ramp when the warning is enabled.
Specifies the Event groups this
warning belongs to.
Enables locked rotor warning.
Setting range
Default value
40.0 ... 99.0 %
90.0 %
Event group 0 ... 6
4
Off, On
Off
Setting range
Default value
0.2 ... 10.0 x I e
3.0 x I e
1.0 ... 30.0 s
1.0 s
Eventgroup 0 ... 6
4
Off, On
Off
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents