7.12.3
Analog output
The softstarter is equipped with one analog output for a
configurable analog output signal to an analog meter, or
the PLC.
The parameter analogue output type, AO type, can be
selected to show:
Motor current, A
Mains voltage, V
Active power, kW
Active power, HP
Reactive power, kVar
Apparent power, kVA
Active energy, kWh
Reactive energy, kVArh
cos fi
Motor temperature, %
Thyristor temperature, %
Motor voltage, %
Mains frequency, Hz
PT100 temperature, centigrade
PTC resistance, Ohm
The voltage or current output can be set by a
configuration parameter, AO reference in the softstarter.
The selection of voltage or current must be set to adapt to
the analog meter or the PLC.
The settings are:
0-10V voltage output
0-10mA current output
0-20mA current output
4-20mA current output
AO is the referens to the output voltage in 0-100 % of the
set parameter AO max and AO min.
Example:
AO type is set to Motor current.
AO reference is set to 0-10V
AO min to 0, and AO max to 3000.
This means that when the motor current is:
3000 A, the output voltage will be 10V.
0 A, the output voltage will be 0 V.
1500 A, the output voltage will be 5 V.