Programmable inputs - terminals 15, 16
5.1.2.4
and 17
WARNING
Terminal Terminal 13, 14 ,15, 16 and 17 should be
connected using 24V DC only. Other voltages may
damage the softstarter and the warranty may no
longer be valid.
The softstarter has three programmable inputs.
In0, default reset event.
In1, default none
In2, default none
For programming the softstarter inputs, see chapter 7
Function settings.
Connect the cables according to Figure 33, 34 or 35
depending on whether internal or external source is used.
Wiring for sequence start, see next page.
L
N
100-250V
50/60 Hz
K4
K5
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
K5
Tightening torques and cable dimensions.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
K6
Start Stop
In0 In1 In2
GND
+24V
K6
Start Stop In0
In1 In2
GND
+24V
33
Figure 33: Terminals 16 and 17
34
L
N
100-250V
50/60 Hz
K4
K5
Figure 34:
Programmable inputs, terminals 15, 16 and 17
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
35
L
N
100-250V
50/60 Hz
K4
K5
Figure 35:
External control voltage
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
K6
Start Stop In0 In1 In2 DGND
GND
+24V
PSTX
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
+
-
DC
K6
Start Stop
In0
In1 In2 DGND
GND
+24V
PSTX
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm