B.4 MEMORY MAPPING
F504
BITFIELD: 3-PHASE ELEMENT STATE
bitmask
element state
0
Pickup
1
Operate
2
Pickup Phase A
B
3
Pickup Phase B
4
Pickup Phase C
5
Operate Phase A
6
Operate Phase B
7
Operate Phase C
F505
BITFIELD: CONTACT OUTPUT STATE
0 = Contact State, 1 = Voltage Detected, 2 = Current Detected
F507
BITFIELD: COUNTER ELEMENT STATE
0 = Count Greater Than, 1 = Count Equal To, 2 = Count Less Than
F509
BITFIELD: SIMPLE ELEMENT STATE
0 = Operate
F511
BITFIELD: 3-PHASE SIMPLE ELEMENT STATE
0 = Operate, 1 = Operate A, 2 = Operate B, 3 = Operate C
F513
ENUMERATION: POWER SWING MODE
0 = Two Step, 1 = Three Step
F514
ENUMERATION: POWER SWING TRIP MODE
0 = Delayed, 1 = Early
F515
ENUMERATION ELEMENT INPUT MODE
0 = Signed, 1 = Absolute
B-80
N60 Network Stability and Synchrophasor Measurement System
F516
ENUMERATION ELEMENT COMPARE MODE
0 = Level, 1 = Delta
F518
ENUMERATION: FLEXELEMENT™ UNITS
0 = Milliseconds, 1 = Seconds, 2 = Minutes
F519
ENUMERATION: NON-VOLATILE LATCH
0 = Reset-Dominant, 1 = Set-Dominant
F522
ENUMERATION: TRANSDUCER DCMA OUTPUT RANGE
0 = –1 to 1 mA; 1 = 0 to 1 mA; 2 = 4 to 20 mA
F523
ENUMERATION: DNP OBJECTS 20, 22, AND 23 DEFAULT
VARIATION
bitmask
default variation
0
1
1
2
2
5
3
6
F524
ENUMERATION: DNP OBJECT 21 DEFAULT VARIATION
bitmask
Default Variation
0
1
1
2
2
9
3
10
F525
ENUMERATION: DNP OBJECT 32 DEFAULT VARIATION
bitmask
default variation
0
1
1
2
2
3
3
4
4
5
5
7
APPENDIX B