B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 55 of 57)
ADDR
REGISTER NAME
EAB3
...Repeated for PMU 4
Phasor Measurement Unit Current Trigger (Read/Write Setting)
EAB4
PMU 1 Current Trigger Function
EAB5
PMU 1 Current Trigger Pickup
EAB6
PMU 1 Current Trigger Pickup Time
B
EAB7
PMU 1 Current Trigger Dropout Time
EAB8
PMU 1 Current Trigger Block (3 items)
EABB
PMU 1 Current Trigger Target
EABC
PMU 1 Current Trigger Events
EABD
...Repeated for PMU 2
EAC6
...Repeated for PMU 3
EACF
...Repeated for PMU 4
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
EAD8
PMU 1 df/dt Trigger Function
EAD9
PMU 1 df/dt Trigger Raise
EADA
PMU 1 df/dt Trigger Fall
EADB
PMU 1 df/dt Trigger Pickup Time
EADC
PMU 1 df/dt Trigger Dropout Time
EADD
PMU 1 df/dt Trigger Block (3 items)
EAE0
PMU 1 df/dt Trigger Target
EAE1
PMU 1 df/dt Trigger Events
EAE2
...Repeated for PMU 2
EAEC
...Repeated for PMU 3
EAF6
...Repeated for PMU 4
Phasor Measurement Unit Frequency Trigger (Read/Write Setting)
EB00
PMU 1 Frequency Trigger Function
EB01
PMU 1 Frequency Trigger Low Frequency
EB02
PMU 1 Frequency Trigger High Frequency
EB03
PMU 1 Frequency Trigger Pickup Time
EB04
PMU 1 Frequency Trigger Dropout Time
EB05
PMU 1 Frequency Trigger Block (3 items)
EB08
PMU 1 Frequency Trigger Target
EB09
PMU 1 Frequency Trigger Events
EB0A
...Repeated for PMU 2
EB14
...Repeated for PMU 3
EB1E
...Repeated for PMU 4
Phasor Measurement Unit Power Trigger (Read/Write Setting)
EB28
PMU 1 Power Trigger Function
EB29
PMU 1 Power Trigger Active
EB2A
PMU 1 Power Trigger Reactive
EB2B
PMU 1 Power Trigger Apparent
EB2C
PMU 1 Power Trigger Pickup Time
EB2D
PMU 1 Power Trigger Dropout Time
EB2E
PMU 1 Power Trigger Block (3 items)
EB31
PMU 1 Power Trigger Target
EB32
PMU 1 Power Trigger Events
EB33
...Repeated for PMU 2
EB3E
...Repeated for PMU 3
EB49
...Repeated for PMU 4
Phasor Measurement Unit Voltage Trigger (Read/Write Setting)
EB54
PMU 1 Voltage Trigger Function
EB55
PMU 1 Voltage Trigger Low Voltage
EB56
PMU 1 Voltage Trigger High Voltage
EB57
PMU 1 Voltage Trigger Pickup Time
B-62
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
0 to 1
---
1
0.1 to 30
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0.1 to 15
Hz/s
0.01
0.1 to 15
Hz/s
0.01
0 to 600
s
0.01
0 to 600
s
0.01
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
20 to 70
Hz
0.01
20 to 70
Hz
0.01
0 to 600
s
0.01
0 to 600
s
0.01
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0.25 to 3
pu
0.001
0.25 to 3
pu
0.001
0.25 to 3
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0.25 to 1.25
pu
0.001
0.75 to 1.75
pu
0.001
0 to 600
s
0.01
APPENDIX B
FORMAT
DEFAULT
F102
0 (Disabled)
F001
1800
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
25
F001
25
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
4900
F001
6100
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
1250
F001
1250
F001
1250
F001
10
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
800
F001
1200
F001
10
GE Multilin