B.4 MEMORY MAPPING
F085
ENUMERATION: POWER SWING SHAPE
0 = Mho Shape, 1 = Quad Shape
F086
ENUMERATION: DIGITAL INPUT DEFAULT STATE
B
0 = Off, 1 = On, 2= Latest/Off, 3 = Latest/On
F090
ENUMERATION: LATCHING OUTPUT TYPE
0 = Operate-dominant, 1 = Reset-dominant
F100
ENUMERATION: VT CONNECTION TYPE
0 = Wye; 1 = Delta
F101
ENUMERATION: MESSAGE DISPLAY INTENSITY
0 = 25%, 1 = 50%, 2 = 75%, 3 = 100%
F102
ENUMERATION: DISABLED/ENABLED
0 = Disabled; 1 = Enabled
F104
ENUMERATION: RESET TYPE
0 = Instantaneous, 1 = Timed, 2 = Linear
F105
ENUMERATION: LOGIC INPUT
0 = Disabled, 1 = Input 1, 2 = Input 2
F106
ENUMERATION: PHASE ROTATION
0 = ABC, 1 = ACB
F108
ENUMERATION: OFF/ON
0 = Off, 1 = On
B-66
N60 Network Stability and Synchrophasor Measurement System
F109
ENUMERATION: CONTACT OUTPUT OPERATION
0 = Self-reset, 1 = Latched, 2 = Disabled
F110
ENUMERATION: CONTACT OUTPUT LED CONTROL
0 = Trip, 1 = Alarm, 2 = None
F112
ENUMERATION: RS485 BAUD RATES
bitmask
value
bitmask
0
300
4
1
1200
5
2
2400
6
3
4800
7
F113
ENUMERATION: PARITY
0 = None, 1 = Odd, 2 = Even
F114
ENUMERATION: IRIG-B SIGNAL TYPE
0 = None, 1 = DC Shift, 2 = Amplitude Modulated
F115
ENUMERATION: BREAKER STATUS
0 = Auxiliary A, 1 = Auxiliary B
F116
ENUMERATION: NEUTRAL OVERVOLTAGE CURVES
0 = Definite Time, 1 = FlexCurve™ A, 2 = FlexCurve™ B,
3 = FlexCurve™ C
F117
ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS
0 = 1×72 cycles, 1 = 3×36 cycles, 2 = 7×18 cycles, 3 = 15×9 cycles
F118
ENUMERATION: OSCILLOGRAPHY MODE
0 = Automatic Overwrite, 1 = Protected
APPENDIX B
value
bitmask
value
9600
8
115200
19200
9
14400
38400
10
28800
57600
11
33600