Phase Current - GE N60 Instruction Manual

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
a) PHASE INSTANTANEOUS OVERCURRENT (ANSI 50P)

PATH: SETTINGS
GROUPED ELEMENTS
 PHASE IOC1
5
The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude. The phase instantaneous overcurrent timing
curves are shown below for form-A contacts in a 60 Hz system.
5-126
SETTING GROUP 1(6)
PHASE IOC1
FUNCTION: Disabled
PHASE IOC1 SIGNAL
MESSAGE
SOURCE: SRC 1
PHASE IOC1
MESSAGE
PICKUP:
PHASE IOC1 PICKUP
MESSAGE
DELAY:
PHASE IOC1 RESET
MESSAGE
DELAY:
PHASE IOC1 BLOCK A:
MESSAGE
Off
PHASE IOC1 BLOCK B:
MESSAGE
Off
PHASE IOC1 BLOCK C:
MESSAGE
Off
PHASE IOC1
MESSAGE
TARGET: Self-reset
PHASE IOC1
MESSAGE
EVENTS: Disabled
N60 Network Stability and Synchrophasor Measurement System

PHASE CURRENT

Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: 0.000 to 30.000 pu in steps of 0.001
1.000 pu
Range: 0.00 to 600.00 s in steps of 0.01
0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
0.00 s
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS
5.6.4 PHASE CURRENT
PHASE IOC 1
GE Multilin