Metering - GE N60 Instruction Manual

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
PHASOR MEASUREMENT UNIT
Output format:
per IEEE C37.118 standard
Number of channels:
14 synchrophasors, 8 analogs, 16 digi-
tals
TVE (total vector error)
<1%
Triggering:
frequency, voltage, current, power, rate
of change of frequency, user-defined
Reporting rate:
1, 2, 5, 10, 12, 15, 20, 25, 30, 50, or 60
times per second
Number of clients:
One over TCP/IP port, two over UDP/IP
ports
AC ranges:
As indicated in appropriate specifications
sections
Network reporting format: 16-bit integer or 32-bit IEEE floating
point numbers
Network reporting style: rectangular (real and imaginary) or polar
(magnitude and angle) coordinates
Post-filtering:
none, 3-point, 5-point, 7-point
Calibration:
±5°
RMS CURRENT: PHASE, NEUTRAL, AND GROUND
Accuracy at
0.1 to 2.0 × CT rating: ±0.25% of reading or ±0.1% of rated
(whichever is greater)
> 2.0 × CT rating:
±1.0% of reading
RMS VOLTAGE
Accuracy:
±0.5% of reading from 10 to 208 V
REAL POWER (WATTS)
Accuracy:
±1.0% of reading at
–0.8 < PF ≤ –1.0 and 0.8 < PF ≤ 1.0
REACTIVE POWER (VARS)
±1.0% of reading at –0.2 ≤ PF ≤ 0.2
Accuracy:
APPARENT POWER (VA)
Accuracy:
±1.0% of reading
WATT-HOURS (POSITIVE AND NEGATIVE)
Accuracy:
±2.0% of reading
±0 to 1 × 10
Range:
Parameters:
three-phase only
Update rate:
50 ms
AC CURRENT
CT rated primary:
1 to 50000 A
CT rated secondary:
1 A or 5 A by connection
Nominal frequency:
20 to 65 Hz
Relay burden:
< 0.2 VA at rated secondary
Conversion range:
Standard CT:
0.02 to 46 × CT rating RMS symmetrical
Sensitive Ground CT module:
0.002 to 4.6 × CT rating RMS symmetrical
Current withstand:
20 ms at 250 times rated
1 sec. at 100 times rated
continuous at 3 times rated
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
6
MWh
VAR-HOURS (POSITIVE AND NEGATIVE)
Accuracy:
±2.0% of reading
±0 to 1 × 10
Range:
Parameters:
three-phase only
Update rate:
50 ms
FREQUENCY
Accuracy at
V = 0.8 to 1.2 pu:
±0.001 Hz (when voltage signal is used
for frequency measurement)
I = 0.1 to 0.25 pu:
±0.05 Hz
I > 0.25 pu:
±0.001 Hz (when current signal is used
for frequency measurement)
DEMAND
Measurements:
Phases A, B, and C present and maxi-
mum measured currents
3-Phase Power (P, Q, and S) present
and maximum measured currents
Accuracy:
±2.0%
Short circuit rating:
150000 RMS symmetrical amperes, 250
V maximum (primary current to external
CT)
AC VOLTAGE
VT rated secondary:
50.0 to 240.0 V
VT ratio:
1.00 to 24000.00
Nominal frequency:
20 to 65 Hz
Relay burden:
< 0.25 VA at 120 V
Conversion range:
1 to 275 V
Voltage withstand:
continuous at 260 V to neutral
1 min./hr at 420 V to neutral
2.2 SPECIFICATIONS

2.2.4 METERING

6
Mvarh
2.2.5 INPUTS
2-9