B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 17 of 57)
ADDR
REGISTER NAME
47AB
Synchrocheck 1 Live V2 Minimum Voltage
47AC
Synchrocheck 1 Target
47AD
Synchrocheck 1 Events
47AE
Synchrocheck 1 Block
47AF
Synchrocheck 1 Frequency Hysteresis
B
47B0
...Repeated for Synchrocheck 2
Demand (Read/Write Setting)
47D0
Demand Current Method
47D1
Demand Power Method
47D2
Demand Interval
47D3
Demand Input
Demand (Read/Write Command)
47D4
Demand Clear Record
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
4C0A
User-Definable Display 1 Bottom Line Text
4C14
Modbus Addresses of Display 1 Items (5 items)
4C19
Reserved (7 items)
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
4C60
...Repeated for User-Definable Display 4
4C80
...Repeated for User-Definable Display 5
4CA0
...Repeated for User-Definable Display 6
4CC0
...Repeated for User-Definable Display 7
4CE0
...Repeated for User-Definable Display 8
4D00
...Repeated for User-Definable Display 9
4D20
...Repeated for User-Definable Display 10
4D40
...Repeated for User-Definable Display 11
4D60
...Repeated for User-Definable Display 12
4D80
...Repeated for User-Definable Display 13
4DA0
...Repeated for User-Definable Display 14
4DC0
...Repeated for User-Definable Display 15
4DE0
...Repeated for User-Definable Display 16
User Programmable Pushbuttons (Read/Write Setting) (12 modules)
4E00
User Programmable Pushbutton 1 Function
4E01
User Programmable Pushbutton 1 Top Line
4E0B
User Programmable Pushbutton 1 On Text
4E15
User Programmable Pushbutton 1 Off Text
4E1F
User Programmable Pushbutton 1 Drop-Out Time
4E20
User Programmable Pushbutton 1 Target
4E21
User Programmable Pushbutton 1 Events
4E22
User Programmable Pushbutton 1 LED Operand
4E23
User Programmable Pushbutton 1 Autoreset Delay
4E24
User Programmable Pushbutton 1 Autoreset Function
4E25
User Programmable Pushbutton 1 Local Lock
4E26
User Programmable Pushbutton 1 Message Priority
4E27
User Programmable Pushbutton 1 Remote Lock
4E28
User Programmable Pushbutton 1 Reset
4E29
User Programmable Pushbutton 1 Set
4E2A
...Repeated for User Programmable Pushbutton 2
4E54
...Repeated for User Programmable Pushbutton 3
4E7E
...Repeated for User Programmable Pushbutton 4
B-24
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
0 to 1.25
pu
0.01
0 to 2
---
1
0 to 1
---
1
0 to 65535
---
1
0 to 0.1
Hz
0.01
0 to 2
---
1
0 to 2
---
1
0 to 5
---
1
0 to 65535
---
1
0 to 1
---
1
0 to 65535
---
1
---
---
---
---
---
---
0 to 65535
---
1
---
---
---
0 to 2
---
1
---
---
---
---
---
---
---
---
---
0 to 60
s
0.05
0 to 2
---
1
0 to 1
---
1
0 to 65535
---
1
0 to 600
s
0.05
0 to 1
---
1
0 to 65535
---
1
0 to 2
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
APPENDIX B
FORMAT
DEFAULT
F001
70
F109
0 (Self-reset)
F102
0 (Disabled)
F300
0
F001
6
F139
0 (Thrm. Exponential)
F139
0 (Thrm. Exponential)
F132
2 (15 MIN)
F300
0
F126
0 (No)
F001
0
F202
" "
F202
""
F001
0
F001
0
F109
2 (Disabled)
F202
(none)
F202
(none)
F202
(none)
F001
0
F109
0 (Self-reset)
F102
0 (Disabled)
F300
0
F001
0
F102
0 (Disabled)
F300
0
F220
0 (Disabled)
F300
0
F300
0
F300
0