Check installation

The installation preparations have been com-
pleted according to the installation checklist.
The drive is mounted securely.
The space around the drive meets the drive's
specifications for cooling
location
The motor and driven equipment are ready for
start.
For IT systems, corner-grounded TN systems
and residual current circuit breakers: the inter-
nal EMC filter is disconnected
ing installation (R1...R4)
of wiring installation (R5...R6)
The drive is properly grounded.
The input power (mains) voltage matches the
drive's nominal input voltage.
The input power (mains) connections at U1, V1
and W1 are connected and tightened as speci-
fied.
The input power (mains) fuses and mains
switch are installed.
cable, fuses and circuit breakers
The motor connections at U2, V2 and W2 are
connected and tightened as specified.
The motor cable is routed away from other
cables.
NO power factor compensation capacitors are
in the motor cable.
The control connections are connected and
tightened as specified.