ABB ACH550-01 User Manual page 151

Hide thumbs Also See for ACH550-01:
Table of Contents

Advertisement

Code Description
5309 EFB STATUS
Contains the status of the EFB protocol.
0 =
– EFB protocol is configured, but not receiving any messages.
IDLE
1 =
EXECUT INIT
2 =
TIME OUT
the network master and the EFB protocol.
3 =
CONFIG ERROR
4 =
-
OFF
LINE
addressed to this drive.
5 =
-
– EFB protocol is receiving messages that are addressed to
ON
LINE
this drive.
6 =
– EFB protocol is performing a hardware reset.
RESET
7 =
LISTEN ONLY
5318 EFB PAR 18
For Modbus only: Slave response delay. Sets additional delay in
milliseconds before the drive begins transmitting response to the
master request.
BACnet-specific communication parameters
5310 EFB PAR 10
Sets the BACnet MS/TP response turn-around time, in milliseconds.
5311 EFB PAR 11
Sets, together with parameter 5317
• For the range 1 to 65535: This parameter sets the ID directly (5317
must be 0). For example, the following values set the ID to 49134:
5311 = 49134 and 5317 = 0.
• For IDs > 65535: The ID equals parameter 5311's value plus 10000
times parameter 5317's value. For example, the following values set
the ID to 71234: 5311 = 1234 and 5317 = 7.
5312 EFB PAR 12
Sets the BACnet Device Object Max Info Frames property.
5313 EFB PAR 13
Sets the BACnet Device Object Max Master property.
5316 EFB PAR 16
Indicates the count of MS/TP tokens passed to this drive.
5317 EFB PAR 17
Works with parameter 5311 to set BACnet instance IDs. See parameter
5311.
146
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
– EFB protocol is initializing.
– A time-out has occurred in the communication between
– EFB protocol has a configuration error.
– EFB protocol is receiving messages that are NOT
– EFB protocol is in listen-only mode.
ACH550-01 User's Manual
Range
0...7
0...65535
0...65535
0...65535
17, BACnet instance IDs:
EFB PAR
0...65535
0...65535
0...65535
0...65535
Serial communications

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ach550