Hardware description
X1
1
SCR
2
AI1
3
AGND
4
+10 V
5
AI2
6
AGND
7
AO1
8
AO2
9
AGND
Technical data
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Hardware description
Terminal for signal cable shield (connected internally to
chassis ground).
Analogue input channel 1, programmable.
2
Default
= frequency reference. Resolution 0.1%,
accuracy ±1%.
Two different DIP switch types can be used.
J1: AI1 OFF: 0...10 V (R
J1: AI1 ON: 0...20 mA (R
Analogue input circuit common (connected internally to
the chassis ground through 1 Mohm).
10 V/10 mA reference voltage output for analogue input
potentiometer (1...10 kohm), accuracy ±2%.
Analogue input channel 2, programmable.
2
Default
= Actual signal 1 (PID1 feedback). Resolution
0.1%, accuracy ±1%.
Two different DIP switch types can be used.
J1: AI2 OFF: 0...10 V (R
J1: AI2 ON: 0...20 mA (R
Analogue input circuit common (connected internally to
the chassis ground through 1 Mohm).
Analogue output, programmable. Default
0...20 mA (load < 500 ohm). Accuracy ±3%.
Analogue output, programmable. Default
0...20 mA (load < 500 ohm). Accuracy ±3%.
Analogue output circuit common (connected internally to
the chassis ground through 1 Mohm).
= 312 kohm)
i
= 100 ohm)
i
= 312 kohm)
i
= 100 ohm)
i
2
= frequency.
2
= current.